ID 70221

Drive is not ready for interpolation.

Description

The CANopen-drive is to be moved, although it is not in the "Operation enabled" state (see documentation of the drive manufacturer). Therefore, it cannot therefore follow the specified setpoints.

 

Possible solutions:

Check if the drive releases in the PLC were set

Possibly the CANopen state must be gone through again after a drive error (Remove drive releases and set them again)

Check whether the drive releases were set in the correct sequence ("Drive On" -> "Torque Permission" -> "Release Feedhold", see [HLI//Control commands of an axis]). Perhaps the releases were set too fast one after the other.

Check the hardware release at the drive amplifier.

Response

Class

5

Immediate stop of the concerned axis

Solution

Class

6

Possible solutions:

  • Check if the drive releases in the PLC were set
  • Possibly the CANopen state must be gone through again after a drive error (Remove drive releases and set them again)
  • Check whether the drive releases have been set in the correct order ("Drive On" ->"Torque Permission" -> "Release Feedhold", [ HLI//Section: Control commands of an axis]). Perhaps the releases were set too fast one after the other.
  • Check the hardware release at the drive amplifier.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of concerned axis.

%2:

Drive type [-]

Drive type P-AXIS-00020 of the affected axis

%3:

Current value [-]

Status word of the drive

%4:

Block number [-]

Block number of the NC program, in which the error occurred

Error type

11, Error message from position controller.