ID 70315

Activation of temperature compensation not possible, since axis is not referenced.

Description

The axis must be homed in order to activate temperature compensation.

See [FCT-C5// Section: Temperature compensation]

Response

Class

1

Warning, temperature compensation remains inactive until axis is homed

Solution

Class

1

Home the axis (see [FCT-M1])

If an absolute measuring system is used, parameter P-AXIS-00014 can be set to 1 to mark the homing of the axis.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of concerned axis

%2:

Error value [-]

TRUE, if axis is homed

Error type

11, Error message from position controller.