ID 294058
Measuring range of force sensor exceeded. | |||
Description | The resolution of the force sensor is -1500 to +6500 increments. Are these values exceeded we do not have a correct signal any more. The reason can be a reset of the sensor under pressure or long time drift in the force signal. | ||
Response | Class | 1 | The value of the force sensor is wrong. |
Solution | Class | 1 | Check if the force value in increments is in between +- 50 INC with an open gun. Check if the reset works properly and is not set under pressure. |
Error type | 11, Error message from position controller. | ||