ID 110549

Invalid bit number for additional 'Ready for Power test'.

Description

Reference monitoring was activated but the bit number configured in P-AXIS-00425 is invalid for reference monitoring.

See FCT-M1// Section: Reference loss (reference monitoring)

 

The smallest permissible value for P-AXIS-00425 is 0.

Depending on the length of the configured telegram element used to transfer the referenced information, the maximum value of this parameter is:

Telegram element length

Maximum value for P-AXIS-00425

2

15

4

31

This error message also occurs if no value was configured for P-AXIS-00425.

Response

Class

3

Reference monitoring is deactivated.

Solution

Class

1

Assign a valid value to P-AXIS-00425 or disable reference monitoring.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

Current value of P-AXIS-00425.

%3:

Limit value [-]

Limit value for P-AXIS-00425.

%4:

Corrected value [-]

Corrected value of P-AXIS-00425.

Error type

2, Error message on data transfer of parameter lists to controller.