ID 110606

Invalid combination of P-AXIS-00704 und P-AXIS-00261 configured.

Description

Axis parameters P-AXIS-00704 and P-AXIS-00261 were assigned contradictory values. If P-AXIS-00261 is set, only the values 'DEFAULT' or 'EDGE_TRIGGERED’ may be used for P-AXIS-00704.

Response

Class

1

Warning output, P-AXIS-00704 is set to 'EDGE_TRIGGERED'.

Solution

Class

1

If the edge detection of the 'gantry_on' signal is to be used, use the following setting: P-AXIS-00704 = 'EDGE_TRIGGERED' and P-AXIS-00261 = 0.

When the edge detection is not to be used, set P-AXIS-00261 = 0 and, depending on the required function, either P-AXIS-00704 = 'DEFAULT' or P-AXIS-00704 = 'ONLY_CONTROL_UNIT'.

Parameter

%1:

Logical axis number [-]

axis number

%2:

Current value [-]

Parameterised value of P-AXIS-00261.

%3:

Incorrect value [-]

Parameterised value of P-AXIS-00704.

%4:

Corrected value [-]

Corrected value of P-AXIS-00261.

Error type

2, Error message on data transfer of parameter lists to controller.